What size mini split does a 600 sq ft bedroom in La Crosse, WI need?

600 ft² bedroom in La Crosse, WI
15,000BTU/hr
12,142 BTU/hr of load at 20.2 BTU/ft² — the figure for 995 cooling degree days
600 ft² bedroom in La Crosse, WI15,000 BTU/hrHead size to buy12,142 BTU/hrCalculated load12,000 BTU/hrWhat the 20 BTU/f…
Head size to buy15,000BTU/hr
Calculated load600 ft² × 20.2 BTU/ft²12,142BTU/hr
BTU per square foot hereinterpolated from La Crosse's 995 cooling degree days20.2BTU/ft²
What the 20 BTU/ft² rule givesthis room needs 1% more than the rule says12,000BTU/hr
Summer design temperature91°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone-11°F
Summer day–night swinga fairly dry climate21°F
Days at or above 90°F15days/yr
Oversize from the size stepa big step — read the note24%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. La Crosse runs 995 cooling degree days, which works out to 20.2 BTU/ft² — so for this bedroom the rule is 1% short. A single national figure has to be wrong somewhere, and this is where.
  • Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
  • 15,000 BTU/hr is 24% above the load, and the gap between head sizes is wide — the next size down is 12,000. In a single room that matters more than it would on a central system: there are no other rooms to absorb the excess capacity. If the room is well insulated and shaded, the smaller head is usually the better buy, and modern inverter compressors modulate down far better than they modulate up.
  • La Crosse is fairly dry — summer nights stay within 21°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. La Crosse designs to -11°F. That is cold enough that a standard head will have lost a large part of its rated capacity by the time it is needed most — check the manufacturer's capacity table at -11°F, not the nameplate, and look at hyper-heat rated equipment.
  • Where these numbers come from. La Crosse Municipal Airport, 9 km from downtown La Crosse, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 600 square foot bedroom in La Crosse, WI needs a head of about 15,000 BTU per hour. The calculated load is 12,142 BTU/hr.

Where that number comes from

La Crosse, WI runs 995 cooling degree days a year, which puts the room at 20.2 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 12,000 BTU/hr.

The winter half of the question

La Crosse, WI designs to -11°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.