ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 800 sq ft living room in Tulsa, OK need?

800 ft² living room in Tulsa, OK
24,000BTU/hr
21,697 BTU/hr of load at 24.7 BTU/ft² — the figure for 2,262 cooling degree days
800 ft² living room in Tulsa, OK24,000 BTU/hrHead size to buy21,697 BTU/hrCalculated load17,600 BTU/hrWhat the 20 BTU/f…
Head size to buy24,000BTU/hr
Calculated load800 ft² × 24.7 BTU/ft² × 1.1 for a living room21,697BTU/hr
BTU per square foot hereinterpolated from Tulsa's 2,262 cooling degree days24.7BTU/ft²
What the 20 BTU/ft² rule givesthis room needs 23% more than the rule says17,600BTU/hr
Summer design temperature98°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone12°F
Summer day–night swinga fairly dry climate20°F
Days at or above 90°F74days/yr
Oversize from the size stepwithin the normal step11%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Tulsa runs 2,262 cooling degree days, which works out to 24.7 BTU/ft² — so for this living room the rule is 23% short. A single national figure has to be wrong somewhere, and this is where.
  • Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
  • 24,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • Tulsa is fairly dry — summer nights stay within 20°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. Tulsa designs to 12°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 12°F in writing.
  • Where these numbers come from. Tulsa International Airport, 11 km from downtown Tulsa, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 800 square foot living room in Tulsa, OK needs a head of about 24,000 BTU per hour. The calculated load is 21,697 BTU/hr.

Where that number comes from

Tulsa, OK runs 2,262 cooling degree days a year, which puts the room at 24.7 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 17,600 BTU/hr.

The winter half of the question

Tulsa, OK designs to 12°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes

Read more