ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 800 sq ft bedroom in Reno, NV need?

800 ft² bedroom in Reno, NV
18,000BTU/hr
17,063 BTU/hr of load at 21.3 BTU/ft² — the figure for 1,219 cooling degree days
800 ft² bedroom in Reno, NV18,000 BTU/hrHead size to buy17,063 BTU/hrCalculated load16,000 BTU/hrWhat the 20 BTU/f…
Head size to buy18,000BTU/hr
Calculated load800 ft² × 21.3 BTU/ft²17,063BTU/hr
BTU per square foot hereinterpolated from Reno's 1,219 cooling degree days21.3BTU/ft²
What the 20 BTU/ft² rule givesthis room needs 7% more than the rule says16,000BTU/hr
Summer design temperature99°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone16°F
Summer day–night swinga dry climate32°F
Days at or above 90°F72days/yr
Oversize from the size stepwithin the normal step5%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Reno runs 1,219 cooling degree days, which works out to 21.3 BTU/ft² — so for this bedroom the rule is 7% short. A single national figure has to be wrong somewhere, and this is where.
  • Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
  • 18,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • Reno is dry — nights fall 32°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
  • Do not forget the winter side. Reno designs to 16°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 16°F in writing.
  • Where these numbers come from. Reno/Tahoe International Airport, 7 km from downtown Reno, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 800 square foot bedroom in Reno, NV needs a head of about 18,000 BTU per hour. The calculated load is 17,063 BTU/hr.

Where that number comes from

Reno, NV runs 1,219 cooling degree days a year, which puts the room at 21.3 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 16,000 BTU/hr.

The winter half of the question

Reno, NV designs to 16°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.