What size mini split does a 800 sq ft bedroom in Hillsboro, OR need?
800 ft² bedroom in Hillsboro, OR
15,000BTU/hr
14,670 BTU/hr of load at 18.3 BTU/ft² — the figure for 699 cooling degree days
| Head size to buy | 15,000BTU/hr |
|---|---|
| Calculated load800 ft² × 18.3 BTU/ft² | 14,670BTU/hr |
| BTU per square foot hereinterpolated from Hillsboro's 699 cooling degree days | 18.3BTU/ft² |
| What the 20 BTU/ft² rule givesthe rule overshoots by 8% here | 16,000BTU/hr |
| Summer design temperature | 92°F |
| Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone | 25°F |
| Summer day–night swinga fairly dry climate | 23°F |
| Days at or above 90°F | 20days/yr |
| Oversize from the size stepwithin the normal step | 2% |
Notes
- The "20 BTU per square foot" rule is a Midwest number. Hillsboro runs 699 cooling degree days, which works out to 18.3 BTU/ft² — so for this bedroom the rule overshoots by 8%. A single national figure has to be wrong somewhere, and this is where.
- Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
- 15,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
- Hillsboro is dry — nights fall 23°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
- Do not forget the winter side. Hillsboro designs to 25°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 25°F in writing.
- Where these numbers come from. Portland International Airport, 31 km from downtown Hillsboro, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.
The short answer
A 800 square foot bedroom in Hillsboro, OR needs a head of about 15,000 BTU per hour. The calculated load is 14,670 BTU/hr.
Where that number comes from
Hillsboro, OR runs 699 cooling degree days a year, which puts the room at 18.3 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 16,000 BTU/hr.
The winter half of the question
Hillsboro, OR designs to 25°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.
Sizing a single room is not sizing a house
There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.
Nearby sizes
- What size mini split does a 800 sq ft bedroom in Edison, NJ need?
- What size mini split does a 800 sq ft bedroom in Las Cruces, NM need?
- What size mini split does a 800 sq ft bedroom in Davenport, IA need?
- What size mini split does a 800 sq ft bedroom in South Bend, IN need?
- What size mini split does a 600 sq ft bedroom in Hillsboro, OR need?
- What size mini split does a 800 sq ft living room in Hillsboro, OR need?
Read more
- Mini Split Blowing Cold Air in Heat Mode — Defrost, UsuallyEvery air-source heat pump does this. Knowing what a defrost cycle looks like is the difference between waiting ten minutes and calling somebody out.
- Mini Split Leaking Water Indoors — Four Causes, One CommonA cooling head makes a couple of litres a day. It leaves through a small pipe with no pump behind it, and that pipe is where nearly every leak starts.
- Multi-Zone Mini Split Not Cooling Every Room — The Minimum Output ProblemThe system is not underpowered. It is oversized for the one room that is calling, and multi-zone units handle that far worse than single-zone ones.