ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 600 sq ft living room in Yakima, WA need?

600 ft² living room in Yakima, WA
15,000BTU/hr
12,665 BTU/hr of load at 19.2 BTU/ft² — the figure for 819 cooling degree days
600 ft² living room in Yakima, WA15,000 BTU/hrHead size to buy12,665 BTU/hrCalculated load13,200 BTU/hrWhat the 20 BTU/f…
Head size to buy15,000BTU/hr
Calculated load600 ft² × 19.2 BTU/ft² × 1.1 for a living room12,665BTU/hr
BTU per square foot hereinterpolated from Yakima's 819 cooling degree days19.2BTU/ft²
What the 20 BTU/ft² rule givesthe rule overshoots by 4% here13,200BTU/hr
Summer design temperature98°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone7°F
Summer day–night swinga dry climate34°F
Days at or above 90°F45days/yr
Oversize from the size stepwithin the normal step18%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Yakima runs 819 cooling degree days, which works out to 19.2 BTU/ft² — so for this living room the rule overshoots by 4%. A single national figure has to be wrong somewhere, and this is where.
  • Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
  • 15,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • Yakima is dry — nights fall 34°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
  • Do not forget the winter side. Yakima designs to 7°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 7°F in writing.
  • Where these numbers come from. Yakima Air Terminal, 4 km from downtown Yakima, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 600 square foot living room in Yakima, WA needs a head of about 15,000 BTU per hour. The calculated load is 12,665 BTU/hr.

Where that number comes from

Yakima, WA runs 819 cooling degree days a year, which puts the room at 19.2 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 13,200 BTU/hr.

The winter half of the question

Yakima, WA designs to 7°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes

Read more