What size mini split does a 600 sq ft living room in Tempe, AZ need?

600 ft² living room in Tempe, AZ
24,000BTU/hr
19,145 BTU/hr of load at 29 BTU/ft² — the figure for 5,080 cooling degree days
600 ft² living room in Tempe, AZ24,000 BTU/hrHead size to buy19,145 BTU/hrCalculated load13,200 BTU/hrWhat the 20 BTU/f…
Head size to buy24,000BTU/hr
Calculated load600 ft² × 29 BTU/ft² × 1.1 for a living room19,145BTU/hr
BTU per square foot hereinterpolated from Tempe's 5,080 cooling degree days29BTU/ft²
What the 20 BTU/ft² rule givesthis room needs 45% more than the rule says13,200BTU/hr
Summer design temperature112°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone37°F
Summer day–night swinga fairly dry climate23°F
Days at or above 90°F173days/yr
Oversize from the size stepa big step — read the note25%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Tempe runs 5,080 cooling degree days, which works out to 29 BTU/ft² — so for this living room the rule is 45% short. A single national figure has to be wrong somewhere, and this is where.
  • Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
  • 24,000 BTU/hr is 25% above the load, and the gap between head sizes is wide — the next size down is 18,000. In a single room that matters more than it would on a central system: there are no other rooms to absorb the excess capacity. If the room is well insulated and shaded, the smaller head is usually the better buy, and modern inverter compressors modulate down far better than they modulate up.
  • Tempe is dry — nights fall 23°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
  • Do not forget the winter side. Tempe designs to 37°F. That is mild enough that heating capacity is not the constraint here; size for cooling and the heating follows.
  • Where these numbers come from. Phoenix Sky Harbor Airport, 13 km from downtown Tempe, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 600 square foot living room in Tempe, AZ needs a head of about 24,000 BTU per hour. The calculated load is 19,145 BTU/hr.

Where that number comes from

Tempe, AZ runs 5,080 cooling degree days a year, which puts the room at 29 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 13,200 BTU/hr.

The winter half of the question

Tempe, AZ designs to 37°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.