ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 600 sq ft living room in Orlando, FL need?

600 ft² living room in Orlando, FL
24,000BTU/hr
18,277 BTU/hr of load at 27.7 BTU/ft² — the figure for 3,978 cooling degree days
600 ft² living room in Orlando, FL24,000 BTU/hrHead size to buy18,277 BTU/hrCalculated load13,200 BTU/hrWhat the 20 BTU/f…
Head size to buy24,000BTU/hr
Calculated load600 ft² × 27.7 BTU/ft² × 1.1 for a living room18,277BTU/hr
BTU per square foot hereinterpolated from Orlando's 3,978 cooling degree days27.7BTU/ft²
What the 20 BTU/ft² rule givesthis room needs 38% more than the rule says13,200BTU/hr
Summer design temperature95°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone38°F
Summer day–night swinga moderately humid climate18°F
Days at or above 90°F107days/yr
Oversize from the size stepa big step — read the note31%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Orlando runs 3,978 cooling degree days, which works out to 27.7 BTU/ft² — so for this living room the rule is 38% short. A single national figure has to be wrong somewhere, and this is where.
  • Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
  • 24,000 BTU/hr is 31% above the load, and the gap between head sizes is wide — the next size down is 18,000. In a single room that matters more than it would on a central system: there are no other rooms to absorb the excess capacity. If the room is well insulated and shaded, the smaller head is usually the better buy, and modern inverter compressors modulate down far better than they modulate up.
  • Orlando is moderately humid — summer nights stay within 18°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. Orlando designs to 38°F. That is mild enough that heating capacity is not the constraint here; size for cooling and the heating follows.
  • Where these numbers come from. Orlando Airport, 14 km from downtown Orlando, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 600 square foot living room in Orlando, FL needs a head of about 24,000 BTU per hour. The calculated load is 18,277 BTU/hr.

Where that number comes from

Orlando, FL runs 3,978 cooling degree days a year, which puts the room at 27.7 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 13,200 BTU/hr.

The winter half of the question

Orlando, FL designs to 38°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.