What size mini split does a 600 sq ft bedroom in Gilbert, AZ need?

600 ft² bedroom in Gilbert, AZ
18,000BTU/hr
17,405 BTU/hr of load at 29 BTU/ft² — the figure for 5,080 cooling degree days
600 ft² bedroom in Gilbert, AZ18,000 BTU/hrHead size to buy17,405 BTU/hrCalculated load12,000 BTU/hrWhat the 20 BTU/f…
Head size to buy18,000BTU/hr
Calculated load600 ft² × 29 BTU/ft²17,405BTU/hr
BTU per square foot hereinterpolated from Gilbert's 5,080 cooling degree days29BTU/ft²
What the 20 BTU/ft² rule givesthis room needs 45% more than the rule says12,000BTU/hr
Summer design temperature112°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone37°F
Summer day–night swinga fairly dry climate23°F
Days at or above 90°F173days/yr
Oversize from the size stepwithin the normal step3%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Gilbert runs 5,080 cooling degree days, which works out to 29 BTU/ft² — so for this bedroom the rule is 45% short. A single national figure has to be wrong somewhere, and this is where.
  • Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
  • 18,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • Gilbert is dry — nights fall 23°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
  • Do not forget the winter side. Gilbert designs to 37°F. That is mild enough that heating capacity is not the constraint here; size for cooling and the heating follows.
  • Where these numbers come from. Phoenix Sky Harbor Airport, 26 km from downtown Gilbert, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 600 square foot bedroom in Gilbert, AZ needs a head of about 18,000 BTU per hour. The calculated load is 17,405 BTU/hr.

Where that number comes from

Gilbert, AZ runs 5,080 cooling degree days a year, which puts the room at 29 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 12,000 BTU/hr.

The winter half of the question

Gilbert, AZ designs to 37°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes

Read more