What size mini split does a 600 sq ft bedroom in Federal Way, WA need?

600 ft² bedroom in Federal Way, WA
9,000BTU/hr
8,779 BTU/hr of load at 14.6 BTU/ft² — the figure for 351 cooling degree days
600 ft² bedroom in Federal Way, WA9,000 BTU/hrHead size to buy8,779 BTU/hrCalculated load12,000 BTU/hrWhat the 20 BTU/f…
Head size to buy9,000BTU/hr
Calculated load600 ft² × 14.6 BTU/ft²8,779BTU/hr
BTU per square foot hereinterpolated from Federal Way's 351 cooling degree days14.6BTU/ft²
What the 20 BTU/ft² rule givesthe rule overshoots by 27% here12,000BTU/hr
Summer design temperature86°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone25°F
Summer day–night swinga fairly dry climate20°F
Days at or above 90°F6days/yr
Oversize from the size stepwithin the normal step3%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Federal Way runs 351 cooling degree days, which works out to 14.6 BTU/ft² — so for this bedroom the rule overshoots by 27%. A single national figure has to be wrong somewhere, and this is where.
  • Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
  • 9,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • Federal Way is fairly dry — summer nights stay within 20°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. Federal Way designs to 25°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 25°F in writing.
  • Where these numbers come from. Seattle-Tacoma Airport, 14 km from downtown Federal Way, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 600 square foot bedroom in Federal Way, WA needs a head of about 9,000 BTU per hour. The calculated load is 8,779 BTU/hr.

Where that number comes from

Federal Way, WA runs 351 cooling degree days a year, which puts the room at 14.6 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 12,000 BTU/hr.

The winter half of the question

Federal Way, WA designs to 25°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.