What size mini split does a 600 sq ft bedroom in East Providence, RI need?

600 ft² bedroom in East Providence, RI
12,000BTU/hr
11,857 BTU/hr of load at 19.8 BTU/ft² — the figure for 911 cooling degree days
600 ft² bedroom in East Providence, RI12,000 BTU/hrHead size to buy11,857 BTU/hrCalculated load12,000 BTU/hrWhat the 20 BTU/f…
Head size to buy12,000BTU/hr
Calculated load600 ft² × 19.8 BTU/ft²11,857BTU/hr
BTU per square foot hereinterpolated from East Providence's 911 cooling degree days19.8BTU/ft²
What the 20 BTU/ft² rule givesthe rule overshoots by 1% here12,000BTU/hr
Summer design temperature89°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone7°F
Summer day–night swinga moderately humid climate18°F
Days at or above 90°F10days/yr
Oversize from the size stepwithin the normal step1%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. East Providence runs 911 cooling degree days, which works out to 19.8 BTU/ft² — so for this bedroom the rule overshoots by 1%. A single national figure has to be wrong somewhere, and this is where.
  • Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
  • 12,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • East Providence is moderately humid — summer nights stay within 18°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. East Providence designs to 7°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 7°F in writing.
  • Where these numbers come from. Providence Green State Airport, 10 km from downtown East Providence, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 600 square foot bedroom in East Providence, RI needs a head of about 12,000 BTU per hour. The calculated load is 11,857 BTU/hr.

Where that number comes from

East Providence, RI runs 911 cooling degree days a year, which puts the room at 19.8 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 12,000 BTU/hr.

The winter half of the question

East Providence, RI designs to 7°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes