ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 600 sq ft bedroom in Butte, MT need?

600 ft² bedroom in Butte, MT
6,000BTU/hr
6,000 BTU/hr of load at 10 BTU/ft² — the figure for 103 cooling degree days
600 ft² bedroom in Butte, MT6,000 BTU/hrHead size to buy6,000 BTU/hrCalculated load12,000 BTU/hrWhat the 20 BTU/f…
Head size to buy6,000BTU/hr
Calculated load600 ft² × 10 BTU/ft²6,000BTU/hr
BTU per square foot hereinterpolated from Butte's 103 cooling degree days10BTU/ft²
What the 20 BTU/ft² rule givesthe rule overshoots by 50% here12,000BTU/hr
Summer design temperature88°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone-19°F
Summer day–night swinga dry climate34°F
Days at or above 90°F6days/yr
Oversize from the size stepwithin the normal step0%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Butte runs 103 cooling degree days, which works out to 10 BTU/ft² — so for this bedroom the rule overshoots by 50%. A single national figure has to be wrong somewhere, and this is where.
  • Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
  • 6,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • Butte is dry — nights fall 34°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
  • Do not forget the winter side. Butte designs to -19°F. That is cold enough that a standard head will have lost a large part of its rated capacity by the time it is needed most — check the manufacturer's capacity table at -19°F, not the nameplate, and look at hyper-heat rated equipment.
  • Where these numbers come from. Butte / Valley Vista Mobile Home Community, 6 km from downtown Butte, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 600 square foot bedroom in Butte, MT needs a head of about 6,000 BTU per hour. The calculated load is 6,000 BTU/hr.

Where that number comes from

Butte, MT runs 103 cooling degree days a year, which puts the room at 10 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 12,000 BTU/hr.

The winter half of the question

Butte, MT designs to -19°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes

Read more