What size mini split does a 600 sq ft bedroom in Bartlesville, OK need?
600 ft² bedroom in Bartlesville, OK
15,000BTU/hr
14,289 BTU/hr of load at 23.8 BTU/ft² — the figure for 1,935 cooling degree days
| Head size to buy | 15,000BTU/hr |
|---|---|
| Calculated load600 ft² × 23.8 BTU/ft² | 14,289BTU/hr |
| BTU per square foot hereinterpolated from Bartlesville's 1,935 cooling degree days | 23.8BTU/ft² |
| What the 20 BTU/ft² rule givesthis room needs 19% more than the rule says | 12,000BTU/hr |
| Summer design temperature | 97°F |
| Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone | 10°F |
| Summer day–night swinga fairly dry climate | 23°F |
| Days at or above 90°F | 76days/yr |
| Oversize from the size stepwithin the normal step | 5% |
Notes
- The "20 BTU per square foot" rule is a Midwest number. Bartlesville runs 1,935 cooling degree days, which works out to 23.8 BTU/ft² — so for this bedroom the rule is 19% short. A single national figure has to be wrong somewhere, and this is where.
- Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
- 15,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
- Bartlesville is dry — nights fall 23°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
- Do not forget the winter side. Bartlesville designs to 10°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 10°F in writing.
- Where these numbers come from. Hominy Municipal, 50 km from downtown Bartlesville, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.
The short answer
A 600 square foot bedroom in Bartlesville, OK needs a head of about 15,000 BTU per hour. The calculated load is 14,289 BTU/hr.
Where that number comes from
Bartlesville, OK runs 1,935 cooling degree days a year, which puts the room at 23.8 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 12,000 BTU/hr.
The winter half of the question
Bartlesville, OK designs to 10°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.
Sizing a single room is not sizing a house
There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.
Nearby sizes
- What size mini split does a 600 sq ft bedroom in Phenix City, AL need?
- What size mini split does a 600 sq ft bedroom in Pahrump, NV need?
- What size mini split does a 600 sq ft bedroom in Spartanburg, SC need?
- What size mini split does a 600 sq ft bedroom in Lewiston, ME need?
- What size mini split does a 500 sq ft bedroom in Bartlesville, OK need?
- What size mini split does a 800 sq ft bedroom in Bartlesville, OK need?
- What size mini split does a 600 sq ft living room in Bartlesville, OK need?
Read more
- Mini Split Blowing Cold Air in Heat Mode — Defrost, UsuallyEvery air-source heat pump does this. Knowing what a defrost cycle looks like is the difference between waiting ten minutes and calling somebody out.
- Mini Split Leaking Water Indoors — Four Causes, One CommonA cooling head makes a couple of litres a day. It leaves through a small pipe with no pump behind it, and that pipe is where nearly every leak starts.
- Multi-Zone Mini Split Not Cooling Every Room — The Minimum Output ProblemThe system is not underpowered. It is oversized for the one room that is calling, and multi-zone units handle that far worse than single-zone ones.