ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 400 sq ft living room in Maple Grove, MN need?

400 ft² living room in Maple Grove, MN
9,000BTU/hr
8,810 BTU/hr of load at 20 BTU/ft² — the figure for 956 cooling degree days
400 ft² living room in Maple Grove, MN9,000 BTU/hrHead size to buy8,810 BTU/hrCalculated load8,800 BTU/hrWhat the 20 BTU/f…
Head size to buy9,000BTU/hr
Calculated load400 ft² × 20 BTU/ft² × 1.1 for a living room8,810BTU/hr
BTU per square foot hereinterpolated from Maple Grove's 956 cooling degree days20BTU/ft²
What the 20 BTU/ft² rule givesthis room needs 0% more than the rule says8,800BTU/hr
Summer design temperature90°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone-10°F
Summer day–night swinga moderately humid climate18°F
Days at or above 90°F11days/yr
Oversize from the size stepwithin the normal step2%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Maple Grove runs 956 cooling degree days, which works out to 20 BTU/ft² — so for this living room the rule is 0% short. A single national figure has to be wrong somewhere, and this is where.
  • Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
  • 9,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • Maple Grove is moderately humid — summer nights stay within 18°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. Maple Grove designs to -10°F. That is cold enough that a standard head will have lost a large part of its rated capacity by the time it is needed most — check the manufacturer's capacity table at -10°F, not the nameplate, and look at hyper-heat rated equipment.
  • Where these numbers come from. Minneapolis-St Paul International, 39 km from downtown Maple Grove, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 400 square foot living room in Maple Grove, MN needs a head of about 9,000 BTU per hour. The calculated load is 8,810 BTU/hr.

Where that number comes from

Maple Grove, MN runs 956 cooling degree days a year, which puts the room at 20 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 8,800 BTU/hr.

The winter half of the question

Maple Grove, MN designs to -10°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes

Read more