ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 400 sq ft living room in Kenner, LA need?

400 ft² living room in Kenner, LA
12,000BTU/hr
11,926 BTU/hr of load at 27.1 BTU/ft² — the figure for 3,567 cooling degree days
400 ft² living room in Kenner, LA12,000 BTU/hrHead size to buy11,926 BTU/hrCalculated load8,800 BTU/hrWhat the 20 BTU/f…
Head size to buy12,000BTU/hr
Calculated load400 ft² × 27.1 BTU/ft² × 1.1 for a living room11,926BTU/hr
BTU per square foot hereinterpolated from Kenner's 3,567 cooling degree days27.1BTU/ft²
What the 20 BTU/ft² rule givesthis room needs 36% more than the rule says8,800BTU/hr
Summer design temperature96°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone33°F
Summer day–night swinga humid climate15°F
Days at or above 90°F83days/yr
Oversize from the size stepwithin the normal step1%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Kenner runs 3,567 cooling degree days, which works out to 27.1 BTU/ft² — so for this living room the rule is 36% short. A single national figure has to be wrong somewhere, and this is where.
  • Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
  • 12,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • Kenner is humid — summer nights stay within 15°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. Kenner designs to 33°F. That is mild enough that heating capacity is not the constraint here; size for cooling and the heating follows.
  • Where these numbers come from. New Orleans Airport, 15 km from downtown Kenner, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 400 square foot living room in Kenner, LA needs a head of about 12,000 BTU per hour. The calculated load is 11,926 BTU/hr.

Where that number comes from

Kenner, LA runs 3,567 cooling degree days a year, which puts the room at 27.1 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 8,800 BTU/hr.

The winter half of the question

Kenner, LA designs to 33°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes