ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 400 sq ft living room in Eugene, OR need?

400 ft² living room in Eugene, OR
9,000BTU/hr
6,929 BTU/hr of load at 15.7 BTU/ft² — the figure for 432 cooling degree days
400 ft² living room in Eugene, OR9,000 BTU/hrHead size to buy6,929 BTU/hrCalculated load8,800 BTU/hrWhat the 20 BTU/f…
Head size to buy9,000BTU/hr
Calculated load400 ft² × 15.7 BTU/ft² × 1.1 for a living room6,929BTU/hr
BTU per square foot hereinterpolated from Eugene's 432 cooling degree days15.7BTU/ft²
What the 20 BTU/ft² rule givesthe rule overshoots by 21% here8,800BTU/hr
Summer design temperature93°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone22°F
Summer day–night swinga dry climate32°F
Days at or above 90°F24days/yr
Oversize from the size stepa big step — read the note30%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Eugene runs 432 cooling degree days, which works out to 15.7 BTU/ft² — so for this living room the rule overshoots by 21%. A single national figure has to be wrong somewhere, and this is where.
  • Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
  • 9,000 BTU/hr is 30% above the load, and the gap between head sizes is wide — the next size down is 6,000. In a single room that matters more than it would on a central system: there are no other rooms to absorb the excess capacity. If the room is well insulated and shaded, the smaller head is usually the better buy, and modern inverter compressors modulate down far better than they modulate up.
  • Eugene is dry — nights fall 32°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
  • Do not forget the winter side. Eugene designs to 22°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 22°F in writing.
  • Where these numbers come from. Mahlon Sweet Field, 14 km from downtown Eugene, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 400 square foot living room in Eugene, OR needs a head of about 9,000 BTU per hour. The calculated load is 6,929 BTU/hr.

Where that number comes from

Eugene, OR runs 432 cooling degree days a year, which puts the room at 15.7 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 8,800 BTU/hr.

The winter half of the question

Eugene, OR designs to 22°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes