ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 400 sq ft living room in Arlington, TX need?

400 ft² living room in Arlington, TX
12,000BTU/hr
11,347 BTU/hr of load at 25.8 BTU/ft² — the figure for 2,793 cooling degree days
400 ft² living room in Arlington, TX12,000 BTU/hrHead size to buy11,347 BTU/hrCalculated load8,800 BTU/hrWhat the 20 BTU/f…
Head size to buy12,000BTU/hr
Calculated load400 ft² × 25.8 BTU/ft² × 1.1 for a living room11,347BTU/hr
BTU per square foot hereinterpolated from Arlington's 2,793 cooling degree days25.8BTU/ft²
What the 20 BTU/ft² rule givesthis room needs 29% more than the rule says8,800BTU/hr
Summer design temperature99°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone20°F
Summer day–night swinga moderately humid climate19°F
Days at or above 90°F88days/yr
Oversize from the size stepwithin the normal step6%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Arlington runs 2,793 cooling degree days, which works out to 25.8 BTU/ft² — so for this living room the rule is 29% short. A single national figure has to be wrong somewhere, and this is where.
  • Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
  • 12,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • Arlington is moderately humid — summer nights stay within 19°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. Arlington designs to 20°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 20°F in writing.
  • Where these numbers come from. Fort Worth, 21 km from downtown Arlington, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 400 square foot living room in Arlington, TX needs a head of about 12,000 BTU per hour. The calculated load is 11,347 BTU/hr.

Where that number comes from

Arlington, TX runs 2,793 cooling degree days a year, which puts the room at 25.8 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 8,800 BTU/hr.

The winter half of the question

Arlington, TX designs to 20°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.