ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 400 sq ft bedroom in Los Angeles, CA need?

400 ft² bedroom in Los Angeles, CA
9,000BTU/hr
7,735 BTU/hr of load at 19.3 BTU/ft² — the figure for 842 cooling degree days
400 ft² bedroom in Los Angeles, CA9,000 BTU/hrHead size to buy7,735 BTU/hrCalculated load8,000 BTU/hrWhat the 20 BTU/f…
Head size to buy9,000BTU/hr
Calculated load400 ft² × 19.3 BTU/ft²7,735BTU/hr
BTU per square foot hereinterpolated from Los Angeles's 842 cooling degree days19.3BTU/ft²
What the 20 BTU/ft² rule givesthe rule overshoots by 3% here8,000BTU/hr
Summer design temperature85°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone42°F
Summer day–night swinga humid climate11°F
Days at or above 90°F5days/yr
Oversize from the size stepwithin the normal step16%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Los Angeles runs 842 cooling degree days, which works out to 19.3 BTU/ft² — so for this bedroom the rule overshoots by 3%. A single national figure has to be wrong somewhere, and this is where.
  • Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
  • 9,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • Los Angeles is humid — summer nights stay within 11°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. Los Angeles designs to 42°F. That is mild enough that heating capacity is not the constraint here; size for cooling and the heating follows.
  • Where these numbers come from. Los Angeles Airport, 18 km from downtown Los Angeles, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 400 square foot bedroom in Los Angeles, CA needs a head of about 9,000 BTU per hour. The calculated load is 7,735 BTU/hr.

Where that number comes from

Los Angeles, CA runs 842 cooling degree days a year, which puts the room at 19.3 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 8,000 BTU/hr.

The winter half of the question

Los Angeles, CA designs to 42°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.