What size mini split does a 300 sq ft living room in Yakima, WA need?
300 ft² living room in Yakima, WA
9,000BTU/hr
6,333 BTU/hr of load at 19.2 BTU/ft² — the figure for 819 cooling degree days
| Head size to buy | 9,000BTU/hr |
|---|---|
| Calculated load300 ft² × 19.2 BTU/ft² × 1.1 for a living room | 6,333BTU/hr |
| BTU per square foot hereinterpolated from Yakima's 819 cooling degree days | 19.2BTU/ft² |
| What the 20 BTU/ft² rule givesthe rule overshoots by 4% here | 6,600BTU/hr |
| Summer design temperature | 98°F |
| Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone | 7°F |
| Summer day–night swinga dry climate | 34°F |
| Days at or above 90°F | 45days/yr |
| Oversize from the size stepa big step — read the note | 42% |
Notes
- The "20 BTU per square foot" rule is a Midwest number. Yakima runs 819 cooling degree days, which works out to 19.2 BTU/ft² — so for this living room the rule overshoots by 4%. A single national figure has to be wrong somewhere, and this is where.
- Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
- 9,000 BTU/hr is 42% above the load, and the gap between head sizes is wide — the next size down is 6,000. In a single room that matters more than it would on a central system: there are no other rooms to absorb the excess capacity. If the room is well insulated and shaded, the smaller head is usually the better buy, and modern inverter compressors modulate down far better than they modulate up.
- Yakima is dry — nights fall 34°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
- Do not forget the winter side. Yakima designs to 7°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 7°F in writing.
- Where these numbers come from. Yakima Air Terminal, 4 km from downtown Yakima, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.
The short answer
A 300 square foot living room in Yakima, WA needs a head of about 9,000 BTU per hour. The calculated load is 6,333 BTU/hr.
Where that number comes from
Yakima, WA runs 819 cooling degree days a year, which puts the room at 19.2 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 6,600 BTU/hr.
The winter half of the question
Yakima, WA designs to 7°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.
Sizing a single room is not sizing a house
There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.
Nearby sizes
- What size mini split does a 300 sq ft living room in Lawrence, KS need?
- What size mini split does a 300 sq ft living room in Quincy, MA need?
- What size mini split does a 300 sq ft living room in Fall River, MA need?
- What size mini split does a 300 sq ft living room in Lynn, MA need?
- What size mini split does a 200 sq ft living room in Yakima, WA need?
- What size mini split does a 400 sq ft living room in Yakima, WA need?
- What size mini split does a 300 sq ft bedroom in Yakima, WA need?
Read more
- Mini Split Blowing Cold Air in Heat Mode — Defrost, UsuallyEvery air-source heat pump does this. Knowing what a defrost cycle looks like is the difference between waiting ten minutes and calling somebody out.
- Mini Split Leaking Water Indoors — Four Causes, One CommonA cooling head makes a couple of litres a day. It leaves through a small pipe with no pump behind it, and that pipe is where nearly every leak starts.
- Multi-Zone Mini Split Not Cooling Every Room — The Minimum Output ProblemThe system is not underpowered. It is oversized for the one room that is calling, and multi-zone units handle that far worse than single-zone ones.