What size mini split does a 300 sq ft living room in Spokane, WA need?

300 ft² living room in Spokane, WA
9,000BTU/hr
6,026 BTU/hr of load at 18.3 BTU/ft² — the figure for 689 cooling degree days
300 ft² living room in Spokane, WA9,000 BTU/hrHead size to buy6,026 BTU/hrCalculated load6,600 BTU/hrWhat the 20 BTU/f…
Head size to buy9,000BTU/hr
Calculated load300 ft² × 18.3 BTU/ft² × 1.1 for a living room6,026BTU/hr
BTU per square foot hereinterpolated from Spokane's 689 cooling degree days18.3BTU/ft²
What the 20 BTU/ft² rule givesthe rule overshoots by 9% here6,600BTU/hr
Summer design temperature93°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone5°F
Summer day–night swinga dry climate26°F
Days at or above 90°F24days/yr
Oversize from the size stepa big step — read the note49%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Spokane runs 689 cooling degree days, which works out to 18.3 BTU/ft² — so for this living room the rule overshoots by 9%. A single national figure has to be wrong somewhere, and this is where.
  • Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
  • 9,000 BTU/hr is 49% above the load, and the gap between head sizes is wide — the next size down is 6,000. In a single room that matters more than it would on a central system: there are no other rooms to absorb the excess capacity. If the room is well insulated and shaded, the smaller head is usually the better buy, and modern inverter compressors modulate down far better than they modulate up.
  • Spokane is dry — nights fall 26°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
  • Do not forget the winter side. Spokane designs to 5°F. That is cold enough that a standard head will have lost a large part of its rated capacity by the time it is needed most — check the manufacturer's capacity table at 5°F, not the nameplate, and look at hyper-heat rated equipment.
  • Where these numbers come from. Spokane International Airport, 9 km from downtown Spokane, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 300 square foot living room in Spokane, WA needs a head of about 9,000 BTU per hour. The calculated load is 6,026 BTU/hr.

Where that number comes from

Spokane, WA runs 689 cooling degree days a year, which puts the room at 18.3 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 6,600 BTU/hr.

The winter half of the question

Spokane, WA designs to 5°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.