ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 300 sq ft living room in Southaven, MS need?

300 ft² living room in Southaven, MS
9,000BTU/hr
8,254 BTU/hr of load at 25 BTU/ft² — the figure for 2,417 cooling degree days
300 ft² living room in Southaven, MS9,000 BTU/hrHead size to buy8,254 BTU/hrCalculated load6,600 BTU/hrWhat the 20 BTU/f…
Head size to buy9,000BTU/hr
Calculated load300 ft² × 25 BTU/ft² × 1.1 for a living room8,254BTU/hr
BTU per square foot hereinterpolated from Southaven's 2,417 cooling degree days25BTU/ft²
What the 20 BTU/ft² rule givesthis room needs 25% more than the rule says6,600BTU/hr
Summer design temperature96°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone18°F
Summer day–night swinga moderately humid climate18°F
Days at or above 90°F65days/yr
Oversize from the size stepwithin the normal step9%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Southaven runs 2,417 cooling degree days, which works out to 25 BTU/ft² — so for this living room the rule is 25% short. A single national figure has to be wrong somewhere, and this is where.
  • Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
  • 9,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • Southaven is moderately humid — summer nights stay within 18°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. Southaven designs to 18°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 18°F in writing.
  • Where these numbers come from. Memphis International Airport, 6 km from downtown Southaven, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 300 square foot living room in Southaven, MS needs a head of about 9,000 BTU per hour. The calculated load is 8,254 BTU/hr.

Where that number comes from

Southaven, MS runs 2,417 cooling degree days a year, which puts the room at 25 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 6,600 BTU/hr.

The winter half of the question

Southaven, MS designs to 18°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes

Read more