What size mini split does a 300 sq ft living room in Salt Lake City, UT need?
300 ft² living room in Salt Lake City, UT
9,000BTU/hr
7,556 BTU/hr of load at 22.9 BTU/ft² — the figure for 1,631 cooling degree days
| Head size to buy | 9,000BTU/hr |
|---|---|
| Calculated load300 ft² × 22.9 BTU/ft² × 1.1 for a living room | 7,556BTU/hr |
| BTU per square foot hereinterpolated from Salt Lake City's 1,631 cooling degree days | 22.9BTU/ft² |
| What the 20 BTU/ft² rule givesthis room needs 14% more than the rule says | 6,600BTU/hr |
| Summer design temperature | 100°F |
| Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone | 13°F |
| Summer day–night swinga dry climate | 25°F |
| Days at or above 90°F | 67days/yr |
| Oversize from the size stepwithin the normal step | 19% |
Notes
- The "20 BTU per square foot" rule is a Midwest number. Salt Lake City runs 1,631 cooling degree days, which works out to 22.9 BTU/ft² — so for this living room the rule is 14% short. A single national figure has to be wrong somewhere, and this is where.
- Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
- 9,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
- Salt Lake City is dry — nights fall 25°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
- Do not forget the winter side. Salt Lake City designs to 13°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 13°F in writing.
- Where these numbers come from. Salt Lake City International Airport, 7 km from downtown Salt Lake City, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.
The short answer
A 300 square foot living room in Salt Lake City, UT needs a head of about 9,000 BTU per hour. The calculated load is 7,556 BTU/hr.
Where that number comes from
Salt Lake City, UT runs 1,631 cooling degree days a year, which puts the room at 22.9 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 6,600 BTU/hr.
The winter half of the question
Salt Lake City, UT designs to 13°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.
Sizing a single room is not sizing a house
There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.
Nearby sizes
- What size mini split does a 300 sq ft living room in Jamaica, NY need?
- What size mini split does a 300 sq ft living room in Huntsville, AL need?
- What size mini split does a 300 sq ft living room in Tacoma, WA need?
- What size mini split does a 300 sq ft living room in Des Moines, IA need?
- What size mini split does a 200 sq ft living room in Salt Lake City, UT need?
- What size mini split does a 400 sq ft living room in Salt Lake City, UT need?
- What size mini split does a 300 sq ft bedroom in Salt Lake City, UT need?
Read more
- Mini Split Blowing Cold Air in Heat Mode — Defrost, UsuallyEvery air-source heat pump does this. Knowing what a defrost cycle looks like is the difference between waiting ten minutes and calling somebody out.
- Mini Split Leaking Water Indoors — Four Causes, One CommonA cooling head makes a couple of litres a day. It leaves through a small pipe with no pump behind it, and that pipe is where nearly every leak starts.
- Multi-Zone Mini Split Not Cooling Every Room — The Minimum Output ProblemThe system is not underpowered. It is oversized for the one room that is calling, and multi-zone units handle that far worse than single-zone ones.