What size mini split does a 300 sq ft bedroom in West Fargo, ND need?

300 ft² bedroom in West Fargo, ND
6,000BTU/hr
5,421 BTU/hr of load at 18.1 BTU/ft² — the figure for 665 cooling degree days
300 ft² bedroom in West Fargo, ND6,000 BTU/hrHead size to buy5,421 BTU/hrCalculated load6,000 BTU/hrWhat the 20 BTU/f…
Head size to buy6,000BTU/hr
Calculated load300 ft² × 18.1 BTU/ft²5,421BTU/hr
BTU per square foot hereinterpolated from West Fargo's 665 cooling degree days18.1BTU/ft²
What the 20 BTU/ft² rule givesthe rule overshoots by 10% here6,000BTU/hr
Summer design temperature89°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone-20°F
Summer day–night swinga fairly dry climate23°F
Days at or above 90°F11days/yr
Oversize from the size stepwithin the normal step11%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. West Fargo runs 665 cooling degree days, which works out to 18.1 BTU/ft² — so for this bedroom the rule overshoots by 10%. A single national figure has to be wrong somewhere, and this is where.
  • Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
  • 6,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • West Fargo is dry — nights fall 23°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
  • Do not forget the winter side. West Fargo designs to -20°F. That is cold enough that a standard head will have lost a large part of its rated capacity by the time it is needed most — check the manufacturer's capacity table at -20°F, not the nameplate, and look at hyper-heat rated equipment.
  • Where these numbers come from. Hector International Airport, 9 km from downtown West Fargo, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 300 square foot bedroom in West Fargo, ND needs a head of about 6,000 BTU per hour. The calculated load is 5,421 BTU/hr.

Where that number comes from

West Fargo, ND runs 665 cooling degree days a year, which puts the room at 18.1 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 6,000 BTU/hr.

The winter half of the question

West Fargo, ND designs to -20°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes