What size mini split does a 300 sq ft bedroom in Provo, UT need?
300 ft² bedroom in Provo, UT
9,000BTU/hr
6,869 BTU/hr of load at 22.9 BTU/ft² — the figure for 1,631 cooling degree days
| Head size to buy | 9,000BTU/hr |
|---|---|
| Calculated load300 ft² × 22.9 BTU/ft² | 6,869BTU/hr |
| BTU per square foot hereinterpolated from Provo's 1,631 cooling degree days | 22.9BTU/ft² |
| What the 20 BTU/ft² rule givesthis room needs 14% more than the rule says | 6,000BTU/hr |
| Summer design temperature | 100°F |
| Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone | 13°F |
| Summer day–night swinga dry climate | 25°F |
| Days at or above 90°F | 67days/yr |
| Oversize from the size stepa big step — read the note | 31% |
Notes
- The "20 BTU per square foot" rule is a Midwest number. Provo runs 1,631 cooling degree days, which works out to 22.9 BTU/ft² — so for this bedroom the rule is 14% short. A single national figure has to be wrong somewhere, and this is where.
- Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
- 9,000 BTU/hr is 31% above the load, and the gap between head sizes is wide — the next size down is 6,000. In a single room that matters more than it would on a central system: there are no other rooms to absorb the excess capacity. If the room is well insulated and shaded, the smaller head is usually the better buy, and modern inverter compressors modulate down far better than they modulate up.
- Provo is dry — nights fall 25°F below the afternoon high, which only happens when there is little water in the air. Latent load is small, so nearly all of the head's capacity goes into temperature. A slightly undersized head is forgiving here: it simply runs longer.
- Do not forget the winter side. Provo designs to 13°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 13°F in writing.
- Where these numbers come from. Salt Lake City International Airport, 66 km from downtown Provo, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.
The short answer
A 300 square foot bedroom in Provo, UT needs a head of about 9,000 BTU per hour. The calculated load is 6,869 BTU/hr.
Where that number comes from
Provo, UT runs 1,631 cooling degree days a year, which puts the room at 22.9 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 6,000 BTU/hr.
The winter half of the question
Provo, UT designs to 13°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.
Sizing a single room is not sizing a house
There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.
Nearby sizes
- What size mini split does a 300 sq ft bedroom in Arvada, CO need?
- What size mini split does a 300 sq ft bedroom in Peoria, IL need?
- What size mini split does a 300 sq ft bedroom in Wilmington, NC need?
- What size mini split does a 300 sq ft bedroom in Springfield, IL need?
- What size mini split does a 200 sq ft bedroom in Provo, UT need?
- What size mini split does a 400 sq ft bedroom in Provo, UT need?
- What size mini split does a 300 sq ft living room in Provo, UT need?
Read more
- Mini Split Blowing Cold Air in Heat Mode — Defrost, UsuallyEvery air-source heat pump does this. Knowing what a defrost cycle looks like is the difference between waiting ten minutes and calling somebody out.
- Mini Split Leaking Water Indoors — Four Causes, One CommonA cooling head makes a couple of litres a day. It leaves through a small pipe with no pump behind it, and that pipe is where nearly every leak starts.
- Multi-Zone Mini Split Not Cooling Every Room — The Minimum Output ProblemThe system is not underpowered. It is oversized for the one room that is calling, and multi-zone units handle that far worse than single-zone ones.