What size mini split does a 300 sq ft bedroom in Lewiston, ME need?

300 ft² bedroom in Lewiston, ME
6,000BTU/hr
4,951 BTU/hr of load at 16.5 BTU/ft² — the figure for 497 cooling degree days
300 ft² bedroom in Lewiston, ME6,000 BTU/hrHead size to buy4,951 BTU/hrCalculated load6,000 BTU/hrWhat the 20 BTU/f…
Head size to buy6,000BTU/hr
Calculated load300 ft² × 16.5 BTU/ft²4,951BTU/hr
BTU per square foot hereinterpolated from Lewiston's 497 cooling degree days16.5BTU/ft²
What the 20 BTU/ft² rule givesthe rule overshoots by 17% here6,000BTU/hr
Summer design temperature86°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone-3°F
Summer day–night swinga moderately humid climate18°F
Days at or above 90°F3days/yr
Oversize from the size stepa big step — read the note21%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Lewiston runs 497 cooling degree days, which works out to 16.5 BTU/ft² — so for this bedroom the rule overshoots by 17%. A single national figure has to be wrong somewhere, and this is where.
  • Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
  • 6,000 BTU/hr is 21% above the load, and the gap between head sizes is wide — this is already the smallest head. In a single room that matters more than it would on a central system: there are no other rooms to absorb the excess capacity. If the room is well insulated and shaded, the smaller head is usually the better buy, and modern inverter compressors modulate down far better than they modulate up.
  • Lewiston is moderately humid — summer nights stay within 18°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. Lewiston designs to -3°F. That is cold enough that a standard head will have lost a large part of its rated capacity by the time it is needed most — check the manufacturer's capacity table at -3°F, not the nameplate, and look at hyper-heat rated equipment.
  • Where these numbers come from. Gray, Me., 22 km from downtown Lewiston, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 300 square foot bedroom in Lewiston, ME needs a head of about 6,000 BTU per hour. The calculated load is 4,951 BTU/hr.

Where that number comes from

Lewiston, ME runs 497 cooling degree days a year, which puts the room at 16.5 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 6,000 BTU/hr.

The winter half of the question

Lewiston, ME designs to -3°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes