ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 200 sq ft living room in Rockville, MD need?

200 ft² living room in Rockville, MD
6,000BTU/hr
5,198 BTU/hr of load at 23.6 BTU/ft² — the figure for 1,868 cooling degree days
200 ft² living room in Rockville, MD6,000 BTU/hrHead size to buy5,198 BTU/hrCalculated load4,400 BTU/hrWhat the 20 BTU/f…
Head size to buy6,000BTU/hr
Calculated load200 ft² × 23.6 BTU/ft² × 1.1 for a living room5,198BTU/hr
BTU per square foot hereinterpolated from Rockville's 1,868 cooling degree days23.6BTU/ft²
What the 20 BTU/ft² rule givesthis room needs 18% more than the rule says4,400BTU/hr
Summer design temperature94°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone16°F
Summer day–night swinga moderately humid climate17°F
Days at or above 90°F40days/yr
Oversize from the size stepwithin the normal step15%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Rockville runs 1,868 cooling degree days, which works out to 23.6 BTU/ft² — so for this living room the rule is 18% short. A single national figure has to be wrong somewhere, and this is where.
  • Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
  • 6,000 BTU/hr sits close to the load, which is where a mini split works best. Inverter equipment is happiest running long and slow at part load; it is the short, hard cycles of an oversized head that leave a room cold and damp.
  • Rockville is moderately humid — summer nights stay within 17°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. Rockville designs to 16°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 16°F in writing.
  • Where these numbers come from. Washington National Airport, 28 km from downtown Rockville, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 200 square foot living room in Rockville, MD needs a head of about 6,000 BTU per hour. The calculated load is 5,198 BTU/hr.

Where that number comes from

Rockville, MD runs 1,868 cooling degree days a year, which puts the room at 23.6 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 4,400 BTU/hr.

The winter half of the question

Rockville, MD designs to 16°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes