ZoneBtuBTU per head, per room, per orientation — not one number for the house.

What size mini split does a 200 sq ft living room in Cambridge, MA need?

200 ft² living room in Cambridge, MA
6,000BTU/hr
4,404 BTU/hr of load at 20 BTU/ft² — the figure for 955 cooling degree days
200 ft² living room in Cambridge, MA6,000 BTU/hrHead size to buy4,404 BTU/hrCalculated load4,400 BTU/hrWhat the 20 BTU/f…
Head size to buy6,000BTU/hr
Calculated load200 ft² × 20 BTU/ft² × 1.1 for a living room4,404BTU/hr
BTU per square foot hereinterpolated from Cambridge's 955 cooling degree days20BTU/ft²
What the 20 BTU/ft² rule givesthis room needs 0% more than the rule says4,400BTU/hr
Summer design temperature90°F
Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone8°F
Summer day–night swinga moderately humid climate16°F
Days at or above 90°F13days/yr
Oversize from the size stepa big step — read the note36%

Notes

  • The "20 BTU per square foot" rule is a Midwest number. Cambridge runs 955 cooling degree days, which works out to 20 BTU/ft² — so for this living room the rule is 0% short. A single national figure has to be wrong somewhere, and this is where.
  • Living room: more people, more glazing, more electronics. The 1.1× factor accounts for that.
  • 6,000 BTU/hr is 36% above the load, and the gap between head sizes is wide — this is already the smallest head. In a single room that matters more than it would on a central system: there are no other rooms to absorb the excess capacity. If the room is well insulated and shaded, the smaller head is usually the better buy, and modern inverter compressors modulate down far better than they modulate up.
  • Cambridge is moderately humid — summer nights stay within 16°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
  • Do not forget the winter side. Cambridge designs to 8°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 8°F in writing.
  • Where these numbers come from. Boston Logan International, 7 km from downtown Cambridge, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.

The short answer

A 200 square foot living room in Cambridge, MA needs a head of about 6,000 BTU per hour. The calculated load is 4,404 BTU/hr.

Where that number comes from

Cambridge, MA runs 955 cooling degree days a year, which puts the room at 20 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 4,400 BTU/hr.

The winter half of the question

Cambridge, MA designs to 8°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.

Sizing a single room is not sizing a house

There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.

Nearby sizes

Read more