What size mini split does a 200 sq ft bedroom in Louisville, KY need?
200 ft² bedroom in Louisville, KY
6,000BTU/hr
4,741 BTU/hr of load at 23.7 BTU/ft² — the figure for 1,895 cooling degree days
| Head size to buy | 6,000BTU/hr |
|---|---|
| Calculated load200 ft² × 23.7 BTU/ft² | 4,741BTU/hr |
| BTU per square foot hereinterpolated from Louisville's 1,895 cooling degree days | 23.7BTU/ft² |
| What the 20 BTU/ft² rule givesthis room needs 19% more than the rule says | 4,000BTU/hr |
| Summer design temperature | 93°F |
| Winter design temperaturea mini split heats too — this is the number that decides whether it can carry the room alone | 10°F |
| Summer day–night swinga moderately humid climate | 18°F |
| Days at or above 90°F | 38days/yr |
| Oversize from the size stepa big step — read the note | 27% |
Notes
- The "20 BTU per square foot" rule is a Midwest number. Louisville runs 1,895 cooling degree days, which works out to 23.7 BTU/ft² — so for this bedroom the rule is 19% short. A single national figure has to be wrong somewhere, and this is where.
- Bedroom: the room where oversizing hurts most — quiet, low load, long runtimes wanted.
- 6,000 BTU/hr is 27% above the load, and the gap between head sizes is wide — this is already the smallest head. In a single room that matters more than it would on a central system: there are no other rooms to absorb the excess capacity. If the room is well insulated and shaded, the smaller head is usually the better buy, and modern inverter compressors modulate down far better than they modulate up.
- Louisville is moderately humid — summer nights stay within 18°F of the day's high, the signature of humid air. A meaningful share of this head's work is removing moisture, and it only removes moisture while it is running. This is the climate where an oversized head produces a room that reads cold and feels clammy.
- Do not forget the winter side. Louisville designs to 10°F. A cold-climate rated head will hold most of its capacity there, but a standard one will not — ask for the capacity at 10°F in writing.
- Where these numbers come from. Standiford Field, 8 km from downtown Louisville, daily records 2015–2024. Design temperatures are calibrated against published ASHRAE values at eight airports and land within about 2°F of them.
The short answer
A 200 square foot bedroom in Louisville, KY needs a head of about 6,000 BTU per hour. The calculated load is 4,741 BTU/hr.
Where that number comes from
Louisville, KY runs 1,895 cooling degree days a year, which puts the room at 23.7 BTU per square foot rather than the 20 BTU/ft² the generic charts use. Applied to this room the rule gives 4,000 BTU/hr.
The winter half of the question
Louisville, KY designs to 10°F. A mini split is a heat pump, and its heating capacity falls as the outdoor temperature drops — the nameplate is measured at 47°F, not at the temperature you actually need it.
Sizing a single room is not sizing a house
There is no other room to absorb a mistake. An oversized head short-cycles, never runs long enough to dehumidify, and leaves the room cold and damp.
Nearby sizes
- What size mini split does a 200 sq ft bedroom in Memphis, TN need?
- What size mini split does a 200 sq ft bedroom in Baltimore, MD need?
- What size mini split does a 200 sq ft bedroom in New South Memphis, TN need?
- What size mini split does a 200 sq ft bedroom in South Boston, MA need?
- What size mini split does a 300 sq ft bedroom in Louisville, KY need?
- What size mini split does a 200 sq ft living room in Louisville, KY need?
Read more
- Mini Split Blowing Cold Air in Heat Mode — Defrost, UsuallyEvery air-source heat pump does this. Knowing what a defrost cycle looks like is the difference between waiting ten minutes and calling somebody out.
- Mini Split Leaking Water Indoors — Four Causes, One CommonA cooling head makes a couple of litres a day. It leaves through a small pipe with no pump behind it, and that pipe is where nearly every leak starts.
- Multi-Zone Mini Split Not Cooling Every Room — The Minimum Output ProblemThe system is not underpowered. It is oversized for the one room that is calling, and multi-zone units handle that far worse than single-zone ones.